Boiler
Furnace Type
|
C-E Tangential Oil/Gas Fired
Furnace
Power Rating: 510 MWe
|
|
Steaming
Rate
|
Steam delivered: 3,558,700
lbm/Hour
|
|
Steam
Conditions
|
Steam temperature at superheater outlet: 1005
F
Steam pressure at superheater outlet: 2500
psig
Steam temperature at reheater outlet: 1000
F
Steam pressure at reheater outlet: 524
PSIG
|
|
Efficiency
|
89.86%
|
|
Burners
|
4 windbox assemblies located in the
furnace corners with adjustable tilting nozzle
tips. Each windox includes five fuel compartments
with a retractable oil gun. Comaprtments between
each fuel compartment are used for admission of
secondary air.
|
|
Fuel Fired
|
256,400 lb/hr
|
|
Gas Temp. Entering Air Heater
|
630 F
|
|
Gas Temp. Leaving Air
Heater
|
291 F
|
|
Air Temp. Entering Air
Heater
|
110
F
|
|
Air Temp. Leaving Air
Heater
|
498
F
|
|
Forced
Draft Fans
|
Two fans with inlet damper
control.
|
|
Recirculation
Fans
|
One fan with variable inlet vane
control.
|
Additional Systems in this PlantSim model include:
|